Voice alarm EN 54 Compact SEVEN-1500R
SEVEN Rack mountable compact public address and voice alarm system EN 54, 3 x 500 W
View specificationsThe SEVEN system can be scaled up to 254 devices connected via TCP/IP data network. Allows the system to be scaled up with control units, paging and firefighter microphones. Each device can operate as an independent node, interconnected by the data network. Live announcements and background music can be transmitted via the data network up to a maximum of 45 audio signals. Connection with Cat5 cable.
Each system is equipped with a control unit with three Class D amplifiers distributing 100 V line signal to 16 speaker zones. The amplifiers can function as a main or backup amplifier, to ensure operation at all times for emergency priority signals. It has monitoring and signalling of system faults and loudspeaker lines. It also has a firefighter's microphone, touch screen control, DSP, buttons and programmable GPI/O inputs and outputs, programmer, 3 simultaneous messages with expandable memory, etc.
The systems integrate a power supply with backup function in case of power loss, in compliance with EN 54-4 standard. Includes a charger.
The system has all elements of a voice alarm system in an rack-mountable enclosure. SEVEN is designed for easy installation and commissioning.
Due to its distributed architecture, the SEVEN system can cover all types of projects and installations, train stations, airports, hotels, shopping centres, stadiums, industrial installations, etc.
FEATURES: | Compact all-in-one public address and voice alarm system EN 54. Based on TCP/IP distributed data network architecture. Integrated DSP, high audio quality. Evacuation functions, alerts, message player and background music. 3 simultaneous messages with 512 MB SDHC internal memory (20 minutes) expandable up to 32 GB. 4'3" touch screen and 4 programmable buttons. Speaker line impedance monitoring. Monitoring and failure detection. Enclosure for 19" rack. Easy installation and commissioning. Simple and intuitive PC configuration software. In compliance with EN 54-16 and EN54-4. |
ZONES: | 16 speaker zones |
POWER: | 3 x 500 RMS |
RESPONSE: | 20-22,000 Hz (@ 0.5 dB/ -3 dB) |
INPUTS: | 1 firefighter microphone 1 stereo input, europlug, 10 kΩ 3 V RMS 7 GPI, euroblock 1 battery temperature sensor, 3.5 mm jack 1 Lan/Wan for PC connection, RJ45 2 Lan, RJ45 |
OUTPUTS: | 16 loudspeaker lines 100 V, Euroblock 2 BUS 1 and 2 local audio line outputs for operation of the 4-line control card 1 stereo output, Scart, 1 V RMS 2 auxiliary power supply outputs, 24 V DC, 150 mA and 48 V DC, 350 mA 3 GPO, euroblock |
TEMPERATURE: | Operation: -5ºC ~ 40ºC Storage: -20ºC ~ 70ºC |
HUMIDITY: | 15% ~ 80% (non-condensing) |
POWER SUPPLY: | 230 V AC, 50/60Hz, 1,600 W (Control unit +48 V DC Battery, Euroblock) |
DIMENSIONS: | 480 x 176 x 354 mm depth, 4U 19" rack |
WEIGHT: | 14 kg |
ACCESSORIES: | Communications microphone (firefighter) Battery cable AC power cable |